| Chilled water pipeline (≥5℃) | ||||
| Flexible foam rubber-plastic shell (mm) | Glass wool shell (mm) | |||
| Nominal pipe diameter | Thickness | Nominal pipe diameter | Thickness | |
| Inside the room ceiling, computer room | 15~25 | 25 | 15~25 | 25 |
| 32~80 | 30 | 32~80 | 30 | |
| ≥100 | 35 | ≥100 | 35 | |
| outdoor | 15~25 | 35 | 15~25 | 30 |
| 32~80 | 40 | 32~80 | 35 | |
| ≥100 | 50 | ≥100 | 40 | |
| Hot water, hot and cold combined pipe (5~60℃) | ||||
| Flexible foam rubber-plastic shell (mm) | Glass wool shell (mm) | |||
| Nominal pipe diameter | Thickness | Nominal pipe diameter | Thickness | |
| Inside the room ceiling, computer room | ≤50 | 30 | ≤40 | 35 |
| 70~150 | 30 | 50~100 | 40 | |
| ≥200 | 35 | 125~250 | 45 | |
| ≥300 | 50 | |||
| Outdoor | ≤50 | 35 | ≤40 | 40 |
| 70~150 | 35 | 50~100 | 45 | |
| ≥200 | 40 | 125~250 | 50 | |
| ≥300 | 55 | |||
| Hot water, hot and cold combined pipe (0~95℃) | ||||
| Polyurethane rigid foam (direct burial) (mm) | Glass wool shell (mm) | |||
| Nominal pipe diameter | Thickness | Nominal pipe diameter | Thickness | |
| Inside the room ceiling, computer room | ≤32 | 30 | ≤50 | 50 |
| 40~200 | 35 | 70~150 | 60 | |
| ≥250 | 45 | ≥200 | 70 | |
| Outdoor | ≤32 | 35 | ≤50 | 60 |
| 40~200 | 40 | 70~150 | 70 | |
| ≥250 | 50 | ≥200 | 80 | |
| Ice storage pipeline (≥-10℃) | ||||
| Flexible foam rubber(mm) | Polyurethane foam (mm) | |||
| Indoor | 15~40 | 35 | 30 | |
| 50~100 | 40 | 40 | ||
| ≥125 | 50 | 50 | ||
| Plate heat exchanger | 35 | - | ||
| Tanks and tanks | 60 | 50 | ||
| Outdoor | 15~40 | 40 | 40 | |
| 50~100 | 50 | 50 | ||
| ≥125 | 60 | 60 | ||
| Tanks and tanks | 70 | 70 | ||
| Air conditioning condensate pipe | ||||
| Flexible foam rubber-plastic shell (mm) | Glass wool shell (mm) | |||
| Air-conditioned room ceiling | 10 | 10 | ||
| Non-air-conditioned room | 15 | 15 | ||
| Air conditioning ducts | ||||
| Flexible foam rubber-plastic board (mm) | Glass wool board, felt (mm) | |||
| Supply air temperature ≥14℃ | In a non-air-conditioned room | 20 | 40 | |
| In an air-conditioned room | 20 | 30 | ||
| Supply air temperature ≥4℃ | In a non-air-conditioned room | 25 | 50 | |
| In an air-conditioned room | 25 | 40 | ||
| Refrigerant pipes (split air conditioners, VRV) | ||||
| Installation Instructions | Required minimum insulation thickness | |||
| 1. Through an air-conditioned space | 19mm | |||
| 2. Through a non-air-conditioned space | 19mm | |||
| 3. Through a bathroom ceiling | 25mm | |||
Thermal Conductivity
Centrifugal Glass Wool λ = 0.031 + 0.00017 tm W/m.K
Flexible Foam Rubber λ = 0.03375 + 0.000125 tm W/m.K
Polyurethane λ = 0.0275 + 0.0009 tm W/m.K
Rigid Polyurethane Foam (Direct Burial) λ = 0.02 + 0.00014 tm W/m.K
Rock Wool or Mineral Wool λ = 0.0314 + 0.0002 tm W/m.K
tm - Average temperature of the insulation layer in °C, calculated as the average temperature of the heat and coolant in the pipe and the surrounding air.